Will this setup pass the rules?

Panels, inverter, plug and battery: check a combination against the GB plug-in rules, with the source for every limit.

max inverter AC output by law
800 W
register entries rated at the full 800 W
184 / 211
compliant kits with more panel than inverter
15 / 28
A British three-pin plug next to a European two-pin plug
Photo: Call Me Fred / Unsplash
1Panels
2panels

Total panel power 890 Wp

2Inverter

AC output

3How it connects

This combination fits the rules

800 W inverter · 890 Wp of panels · 111% panel to inverter

Inverter output (AC)800 W / 800 W limit
Panels (DC)890 W / 2,000 W limit
  • Inverter output 800 WWithin the 800W AC limit. Why
  • 890 W of panels (DC)Within the panel limits. Why
  • Output clippingAbout 10% more panel than inverter: you'll lose a little at midday in summer. Why
  • No batteryFine. Why
  • PlugMoulded BS 1363 plug, 5A fuse or less. Why
  • ConnectionStraight into a fixed socket. Why

The whole kit must also be listed as Compliant on the ENA register: a self-assembled mix of parts usually isn’t. Check a kit.

The rules

Every limit the checker tests, and where it comes from

Plug-in solar has been legal in England, Scotland and Wales since 27 August 2026 under SI 2026/848. The detail is in the DESNZ Interim Product Specification (IPS) and the amended G98 network code.

PartRuleSource
Inverter outputNo more than 800 W AC (800 VA, 3.5 A)SI 2026/848; IPS
PanelsNo more than 2,000 W DC in total. Above 960 W the manufacturer must advise a wiring assessmentIPS §4.1
Panel wiringUp to 4 modules, no more than 2 in series, 120 V DC open-circuit at most, no Y-connectorsIPS
PlugMoulded, non-rewireable BS 1363-1 plug with a fuse of 5 A or lessIPS; SI 2026/848
SocketA fixed BS 1363-2 socket on a socket circuit. No extension leads or adaptorsIPS; Explanatory Memorandum
OutdoorsOutdoor parts and outdoor sockets rated at least IP55IPS
BatteryNone, built in or plug-inSI 2026/848; IPS §1; Ofgem
LeakageDevice DC residual current of 5 mA or lessIPS
The whole kitListed as Compliant on the ENA Type Test RegisterIPS
Per homeOne plug-in kit per householdG98 (Ofgem)
With rooftop solarAllowed if the total stays within 16 A per phaseG98 (Ofgem)

The specification is interim. The Explanatory Memorandum says a full revision of the underlying British Standards is planned "within around 2-3 years". The rules don't yet apply in Northern Ireland: see plug-in solar in Northern Ireland.

Live data

How real kits pair panels with inverters

15 of the 28 compliant kits we track put more panel behind the inverter than it can pass on. That's allowed, and it's why the checker treats clipping as a note rather than a problem.

14

Up to 800 Wp

Panels no bigger than the inverter. No clipping.

8 in stock now

10

801 to 960 Wp

A little more panel than inverter. Clips at summer midday, gains in dull weather.

7 in stock now

4

961 to 2,000 Wp

Allowed. The manufacturer must advise you to consider a wiring assessment.

3 in stock now

Compliant kits we track with a known panel rating (28). The largest has 1,260 Wp of panels. Browse them on all kits or in stock now.

Rated output on the ENA register

AC outputEntriesCompliant
800 W184147
799 W84
500 W109
475 W11
455 W11
440 W10
400 W43
340 W22

From the ENA plug-in register. Smaller inverters suit one-panel kits.

Common mistakes

Setups that don't pass

Each of these breaks a specific rule in the specification or G98, even when the parts work on their own.

A European kit with a plug adaptor

A Schuko plug into a travel adaptor fails twice: the plug must be a moulded BS 1363 plug, and adaptors aren't allowed. Fitting a UK plug yourself doesn't fix it either.

Read the rule

An extension lead to the balcony

The kit must go straight into a fixed wall socket, even an outdoor one. If there's no socket in reach, a new one is electrical work for a registered electrician.

Read the rule

A kit with a balcony battery

The plug-in rules don't cover batteries, whether they're built in or plug in. A battery needs an electrician to wire it in and notify your network operator.

Read the rule

Two kits on two circuits

The product specification would allow one per circuit, but G98 takes precedence and allows one per household until it's amended.

Read the rule

Panels and an inverter bought separately

A standalone inverter or a panel with a DIY plug isn't a compliant kit. Only a complete kit listed as Compliant on the ENA register is.

Read the rule

Five panels, or a Y-connector

The specification allows up to four modules, no more than two in series, and bans Y-connectors, even when the total stays under 2,000 W.

Read the rule

Sizing

Why panels can be bigger than 800 W

The legal cap is on what the inverter feeds into your wiring. Under the G98 change approved by Ofgem, a kit's registered capacity is the lower of the inverter and panel ratings, which in practice is the inverter's AC output.

Panels rarely make their full rating in the UK. Extra panel lifts output in the mornings, evenings and on cloudy days, and costs a little at summer midday when the inverter clips. The checker shows that loss as a percentage.

The limits on the panel side are 2,000 W DC, up to four modules and no more than two in series (IPS). Also check the inverter's own datasheet: each input has a maximum, and that's what the optional DC input box in the checker is for. For the trade-off in numbers, see 400 W vs 800 W.

Your home

Checking your socket and wiring

  • No dedicated circuit needed. The specification covers connection "without requiring installation of a separate electrical circuit for export".
  • A socket circuit only. Not a lighting circuit, and not a spur feeding fixed equipment such as a cooker or boiler.
  • Modern protection. The specification says to check for RCBOs. Homes with older fuses and no RCBOs should be checked and upgraded by an electrician.
  • A stronger recommendation. Electrical Safety First recommends at least a Type A bidirectional RCD. That's advice, not law.
  • One kit per home. G98 allows one per household for now, confirmed in the Government Response.

More in sockets and wiring. If you're unsure what's in your consumer unit, ask a registered electrician rather than opening it yourself.

Plug-in solar compatibility: questions

Can I connect more than 800 W of solar panels to a plug-in inverter?

Yes. The 800 W limit is on the inverter's AC output. The DESNZ specification allows up to 2,000 W of panels (DC), and asks manufacturers to advise a professional wiring assessment above 960 W. 15 of the 28 compliant kits we track have more panel than inverter output.

Will a 1,000 W or 1,200 W inverter work if I limit it to 800 W?

Only if that exact kit is listed as Compliant on the ENA register. The law defines a plug-in microgenerator by a maximum rated AC output of 800 W or less, and each register entry shows the rated output. A larger inverter you've set up yourself isn't a registered kit.

Can I use an extension lead with plug-in solar?

No. The kit must plug straight into a fixed BS 1363-2 wall socket. Extension leads, multi-way adaptors, travel adaptors and plug-in RCD adaptors are all ruled out by the DESNZ specification.

Can I add a battery to my plug-in solar kit?

Not as a plug-in. The law's definition of a plug-in microgenerator excludes devices that store energy from your home's wiring for later, and the specification excludes battery systems. You can still have a battery, but it needs an electrician to wire it in and notify your network operator.

Do I need a special socket or circuit?

No dedicated circuit is needed. The socket must be a fixed socket on a socket circuit, not a lighting circuit or a spur feeding fixed equipment, and IP55 if it's outdoors. The specification says to check you have modern residual current protection (RCBO); homes with older fuses should be checked by an electrician.

Can I add plug-in solar if I already have solar panels on the roof?

Yes, if the combined output stays within 16 A per phase, according to the G98 change Ofgem approved. Above that the larger G99 process applies. Ask the installer of your rooftop system or a registered electrician if you're not sure.

Sources

  1. SI 2026/848: definition of plug-in microgenerator
  2. Explanatory Memorandum to SI 2026/848
  3. DESNZ Plug-in Solar Device Interim Product Specification, v2.0 (July 2026)
  4. Ofgem decision approving DCRP/MP/26/02 (G98 Issue 2 Amendment 1), 11 Aug 2026
  5. DESNZ Government Response, July 2026
  6. ENA Connect Direct Type Test Register (Plug-in Solar)
  7. Electrical Safety First: plug-in solar panels